Fault and Bypass

indicator LEDs and

diagnostic LED D

are illuminated.

UPS PFC (Power Factor Cor-

rection Circuit) fault.

UPS requires service. Contact

your local dealer, Liebert repre-

sentative or the Liebert World-

wide Support Group.

Fault and Bypass

indicator LEDs and

diagnostic LED E are

illuminated.

UPS inverter fault.

UPS requires service. Contact

your local dealer, Liebert Rep-

resentative or the Liebert

Worldwide Support Group.

Fault indicator LED

and diagnostic

LED A and C are illu-

minated.

UPS failed the battery test.

Replace batteries. Contact your

local dealer, Liebert representa-

tive or the Liebert Worldwide

Support Group.

Fault and Bypass

indicator LEDs and

diagnostic LED C

and E are illumi-

nated.

UPS shutdown due to a com-

mand from the communica-

tions port(s).

Your UPS has received a signal

or command from the attached

computer. If this was inadvert-

ent, ensure the communication

cable used is correct for your

system. For assistance, con-

tact your local dealer, Liebert

representative or the Liebert

Worldwide Support Group.

AC LED is

flashing.

UPS detected a line-to-neutral

reversal or a loss of proper

grounding; continuous horn and

UPS will not start.This is active

only when power is first applied

to the input. Once the UPS is

running, the AC LED will not

start flashing, even if the input

wiring is changed.

Contact a qualified electrician to

verify site wiring.

Battery LED is

flashing.

Battery source is not available;

continuous horn.

Check battery connections,

completely power down and

restart UPS.

NOTE: If the battery circuit

opens while the UPS is running,

it will be detected when the next

battery test is performed.

Bypass LED is

flashing.

Bypass voltage is present, but

is disabled for use because the

voltage or frequency is outside

acceptable limits.

The AC input powers the PFC

input and serves as the bypass

source. If the AC is present but

the voltage or frequency

exceeds the acceptable range

for safe operation with a load,

the bypass will be disabled and

this LED will flash, indicating

that the bypass is unavailable.

Troubleshooting Guide (Continued)

Problem

Cause

Solution