Troubleshooting guide – Emerson GXT2U User Manual

Page 30

background image

26

Troubleshooting Guide

Problem

Cause

Solution

UPS fails to start

when the ON button

is pressed.

UPS is short circuited or over-

loaded.

Ensure UPS is OFF. Disconnect

all loads and ensure nothing is

lodged in output receptacles.

Ensure loads are not defective

or shorted internally.

Battery indicator

LED is illuminated.

UPS not plugged in.

UPS is operating from battery

mode, make certain UPS is

securely plugged into the wall

receptacle.

UPS input protection fuse has

blown/opened.

UPS is operating from battery

mode. Save data and close

applications. Replace UPS

input fuse, then restart UPS.

Utility voltage out of UPS input

range.

UPS is operating from battery

mode. Save data and close

applications. Ensure utility sup-

ply voltage is within acceptable

limits for UPS.

UPS has reduced

battery time.

Batteries are not fully charged.

Keep UPS plugged in continu-

ously at least 24 hours to

recharge batteries.

UPS is overloaded.

Check load level display and

reduce the load on the UPS.

Batteries may not be able to

hold a full charge due to age.

Replace batteries. Contact your

local dealer, Liebert representa-

tive or the Liebert Worldwide

Support Group for replacement

battery kit.

Fault and Bypass

indicator LEDs and

all load level LEDs

are illuminated.

UPS overloaded or load equip-

ment is faulty.

Check load level display and

remove non-essential loads.

Recalculate the load and

reduce number of loads con-

nected to UPS. Check load

equipment for faults.

Fault and Bypass

indicator LEDs and

diagnostic LED A are

illuminated.

UPS internal fan has a problem

or UPS shutdown due to tem-

perature condition. Load is on

bypass power.

Ensure UPS is not overloaded,

ventilation openings not

blocked, or room ambient tem-

perature is not excessive. Wait

30 minutes to allow UPS to

cool, then restart UPS. If UPS

does not restart, contact your

local dealer, Liebert representa-

tive or the Liebert Worldwide

Support Group.

Fault and Bypass

indicator LEDs and

diagnostic LED B are

illuminated.

UPS internal DC bus overvolt-

age.

UPS requires service. Contact

your local dealer, Liebert repre-

sentative or the Liebert World-

wide Support Group.

Fault and Bypass

indicator LEDs and

diagnostic LED C

are illuminated.

UPS control power supply fault.

UPS requires service. Contact

your local dealer, Liebert repre-

sentative or the Liebert World-

wide Support Group.