Standby/Manual Bypass Button

This button controls output power to connected load(s) and has dual

functions: Standby and Manual Bypass.

Load/Battery Level Indicators (4 Green, 1 Amber)

The load/battery level indicators have dual functions. During normal mode

operation LED indicators display the approximate electrical load placed upon

the UPS; and during battery mode operation LED indicators display

approximate battery capacity.
The Liebert GXT2U is equipped with automatic and remote battery test

features. The automatic test occurs every 14 days (this option is user

configurable) if utility has not been interrupted. Should the battery fail this

test, the red Fault indicator LED along with the A and C diagnostic LEDs will

illuminate and an alarm will sound (refer to Troubleshooting section). The

remote test feature functions with Liebert MultiLink 3 software and can

remotely initiate the battery test.

Fault Indicator LED (Red)

The Fault indicator LED is illuminated if the UPS has detected a problem.

Also, one or more of the load/battery level indicators may be illuminated (refer

to Troubleshooting section).

Bypass Indicator LED (Amber)

The Bypass indicator LED is illuminated when the UPS is operating from

bypass power. An alarm will sound indicating the UPS detected a problem, or

the manual bypass function has been activated.

UPS ON Indicator LED (Green)

The UPS ON indicator LED is illuminated when the UPS inverter is operating

and supplying power to your connected loads.

Battery Indicator LED (Amber)

The Battery indicator LED is illuminated when the UPS is operating on

battery.

AC Input Indicator LED (Green)

The AC Input indicator LED is illuminated when utility power is available

and within the input specifications.

!

CAUTION

While the UPS is in Normal Mode operation, pressing the Standby/

Manual Bypass button once will put the UPS into Bypass Mode.

Once the UPS is in Bypass Mode operation, press the Standby/

Manual Bypass button two distinct times (for about one second each

time) to turn off the UPS. Perform all necessary shutdown

procedures on connected loads before turning off the UPS.