beautypg.com

Dh485 configuration error word, 3 dh485 configuration error word – ProSoft Technology 5201-DFNT-DH485 User Manual

Page 31

background image

Serial Port Protocol Error/Status Data

DH485 ♦ ProLinx Gateway

Driver Manual

DH485 Interface


ProSoft Technology, Inc.

Page 31 of 44

August 27, 2009

Error #

Description

0x0809

Too many fields in request message

0x080A

Symbol not found

0x080B

Symbol 0 or greater than maximum characters permitted in message

0x080C

Does not exist, illegal size

0x080D

File wrong size, address past end of file

0x080E

Data or file too large (memory not available)

0x080F

Request too large to transmit message (size+address > max message)

0x0810 Access

denied

0x0811

Command cannot be executed

0x0812

Illegal data type information

0x0813

Illegal parameter, invalid data in search or command block

0x0814

File open by another node

0x0815

Program owned by another node

0x0816

Unknown error returned from host

0x0817

No message active on the port

4.2.3 DH485 Configuration Error Word

Bit Code

Description

0

0x0001

Invalid baud rate

1

0x0002

Invalid node address

2

0x0004

Invalid maximum node address

3

0x0008

Invalid token hold factor

4

0x0010

Invalid response timeout

5

0x0020

Invalid status or command error DB offset

6

0x0040

Invalid CIF read count or DB offset

7

0x0080

Invalid CIF write DB offset

8

0x0100

Invalid file size

9

0x0200

Invalid file offset

10 0x0400

11 0x0800

12 0x1000

13 0x2000

14 0x4000

15 0x8000

This manual is related to the following products: