Dh485 port x, Baud rate, Node address – ProSoft Technology 5201-DFNT-DH485 User Manual
Page 21: Maximum node address

Configure the Module
DH485 ♦ ProLinx Gateway
Driver Manual
DH485 Interface
ProSoft Technology, Inc.
Page 21 of 44
August 27, 2009
3.4
[DH485 Port x]
General configuration information for the specified DH-485 port on the module
3.4.1 Baud Rate
Range 1200 to 19200
This is the baud rate to use for the DH485 network. Select one of the listed baud
rates.
3.4.2 Node Address
Range 0 to 31
This is the node address to be utilized by the DH-485 driver for this port on the
network. Enter a value not already used on the network in the range of 0 to 31. If
a value of 255 is utilized or set by the module, the port is disabled. Note: All
nodes on the network should be set to the lowest set of values in the range of 1
to 4).
3.4.3 Maximum Node Address
Range 0 to 31
Enter the maximum address that the initiator searches for before wrapping to
zero. The default is 31. This parameter should be set to the maximum node
address set in the DH-485 network.