ProSoft Technology ILX34-MBS485 User Manual
Page 32

General Features & Specifications
Page 32 of 34
ProSoft Technology, Inc.
February 18, 2015
4.2
Hardware Specifications
Pointbus Current
75 mA @ 5 VDC
Number of Inputs
1 Dull duplex
Module Location
1734-TB or
–TBS wiring base assembly (not included)
LED Indicators
1 green/red module status indicator
1 green/red network status indicator
2 green TXD, RXD status indicators
Operating Temperature
-4°F to 131°F (-20°C to 55°C)
Storage Temperature
-40°F to 185°F (-40°C to 85°C)
Relative Humidity
5% to 95% RH with no condensation
Dimensions
(H x W x L)
2.21 x 0.47 x 2.97 in
56 x 12 x 75.5 mm
Shock
30g Peak acceleration (operating)
50g Peak acceleration (non-operating)
Vibration
Tested 5g @ 10 to 500 Hz
ESD Immunity
6 kV contact discharges
8 kV air discharges
4.3
Agency Approvals
Agency
Applicable Standard(s)
UL/cUL
Class 1, Div. 2 Groups A, B, C, D
ATEX
Category 3, Zone 2
CE Mark
CB Safety