3.7

Data Handling

These are the PLC data tags that are use for the Master and Slave. For the
Master, the following tags represent the internal addresses used by the Master
commands. For the Slave, the following tags represent the addresses accessed
by a remote Master.

Label

Description

InputBit

Incoming discreet data for address
ranges 0x and 1x from other devices.
Functions 5 and 15 when device is
configured as a Slave. Functions and 1
and 2 when configured as a Master.

InputRegister

Incoming register data for address
ranges 3x and 4x from other devices.
Functions 6 and 16 when device is
configured as a Slave. Functions and 3
and 4 when configured as a Master.

OutputBit

Outgoing discreet data for address
ranges 0x and 1x from other devices.
Functions 1 and 2 when device is
configured as a Slave. Functions and 5
and 15 when configured as a Master.

OutputRegister

Outgoing register data for address
ranges 3x and 4x from other devices.
Functions 3 and 4 when device is
configured as a Slave. Functions and 6
and 16 when configured as a Master.