5.1.8 Configuration Data Transfer
When the module performs a restart operation, it will request configuration
information from the PLC processor. This data is transferred to the module in a
specially formatted write block when the BTR/BTW interface is used. The module
will poll for the block by setting the Block Sequence Number in the read block to
a value of 9000. The format of the configuration BTW block is shown below:
When the side-connect interface is used, the module will read the configuration
information directly from the specified application user data file. The format of this
file is shown below:
Word Offset
Description
0 BPFail
1
Enabled
2
Termination Type
3
Baud Rate
4
Parity
5
Data Bits
6
Stop Bits
7
RTS On Delay
8
RTS Off Delay
9
Handshaking
10
Receive Termination Character Count
11 to 16
Receive Termination Characters
17
Receive Packet Length
18
Receive Message Timeout
19
Receive Intercharacter Delay Timeout
20
Transmit Message Timeout
Port 1
21
Minimum Message Transmit Delay
22
Enabled
23
Termination Type
24
Baud Rate
25
Parity
26
Data Bits
27
Stop Bits
28
RTS On Delay
29
RTS Off Delay
30
Handshaking
31
Receive Termination Character Count
32 to 37
Receive Termination Characters
38
Receive Packet Length
39
Receive Message Timeout
40
Receive Intercharacter Delay Timeout
41
Transmit Message Timeout
Port 2
42
Minimum Message Transmit Delay