ProSoft Technology MVI71-GSC User Manual
Page 30

MVI71-GSC ♦ PLC Platform
Installing and Configuring the Module
Generic Serial Communication Module
Page 30 of 82
ProSoft Technology, Inc.
January 31, 2008
Error
Bit in
Word
Description
Cfg_Rtermcount
Bit 6
The number of termination characters is not valid. The value
must be set between 1 and 12 when using the termination
character string to end a receive buffer. The module will not
terminate a buffer when using the termination character(s)
when this bit is set.
Cfg_RPacketLen
Bit 7
The number of characters for a packet is not valid. The value
must be set between 1 and 4096 when the packet size
termination option is used. The module will not use the
packet length termination option when this bit is set.
Cfg_Rtimeout
Bit 8
The message timeout value is set to zero. The module will
not use the message timeout termination option when this bit
is set.
Cfg_Rdelay
Bit 9
The intercharacter delay value configured is set to zero. The
module will not use the intercharacter delay option when this
bit is set.
Cfg_Wtimeout
Bit 10
The write message timeout parameter is set to zero. The
module assumes a value of 5000 milliseconds.
Bit 11
Bit 12
Bit 13
Bit 14
Err_ROverflow
Bit 15
Data is being received faster on the port than the ladder logic
can process the read blocks. Alter the configuration of the
module or the connected device. Receive data is being lost.