MVI71-GSC ♦ PLC Platform

Installing and Configuring the Module

Generic Serial Communication Module

Page 30 of 82

ProSoft Technology, Inc.

January 31, 2008

Error

Bit in
Word

Description

Cfg_Rtermcount

Bit 6

The number of termination characters is not valid. The value
must be set between 1 and 12 when using the termination
character string to end a receive buffer. The module will not
terminate a buffer when using the termination character(s)
when this bit is set.

Cfg_RPacketLen

Bit 7

The number of characters for a packet is not valid. The value
must be set between 1 and 4096 when the packet size
termination option is used. The module will not use the
packet length termination option when this bit is set.

Cfg_Rtimeout

Bit 8

The message timeout value is set to zero. The module will
not use the message timeout termination option when this bit
is set.

Cfg_Rdelay

Bit 9

The intercharacter delay value configured is set to zero. The
module will not use the intercharacter delay option when this
bit is set.

Cfg_Wtimeout

Bit 10

The write message timeout parameter is set to zero. The
module assumes a value of 5000 milliseconds.

Bit 11

Bit 12

Bit 13

Bit 14

Err_ROverflow

Bit 15

Data is being received faster on the port than the ladder logic
can process the read blocks. Alter the configuration of the
module or the connected device. Receive data is being lost.