Led status indicators, Status, Indicators – ProSoft Technology MVI71-GSC User Manual
Page 43

Diagnostics and Troubleshooting
MVI71-GSC ♦ PLC Platform
Generic Serial Communication Module
ProSoft Technology, Inc.
Page 43 of 82
January 31, 2008
When you have captured the data you want to save, open the Transfer menu and
choose Capture Text. On the secondary menu, choose Stop.
You have now captured, and saved the file to your PC. This file can now be used
in analyzing the communications traffic on the line, and assist in determining
communication errors.
1.11 LED Status Indicators
The LEDs will indicate the module's operating status as follows:
ProSoft
Module
Color Status Indication
On
Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.
CFG Green
Off
No data is being transferred on the Configuration/Debug
port.
On
Data is being transferred between the module and the serial
network on its Port 1.
P1 Green
Off
No data is being transferred on the port.
On
Data is being transferred between the module and the serial
network on its Port 2.
P2 Green
Off
No data is being transferred on the port.
On /
Blinking
The MVI71-GSC is operating normally.
APP STS
Amber
Off
The MVI71-GSC module is not operating normally. During
normal operation, the LED should blink rapidly on and off.
On
The LED is on when the module is transferring data on the
backplane.
BP
Amber
Off
The LED is off when the module is not transferring data on
the backplane. During normal operation, the LED should
blink rapidly on and off.
Off
The card is not receiving any power or is not securely
plugged into the rack.
Green
The module is operating normally.
OK Red/
Green
Red
The module has detected a configuration error or has not
been properly configured. If the LED remains red for over 10
seconds, the module has halted and is not functioning
normally.
On
The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.
BAT Red
Off
The battery voltage is OK and functioning.