ProSoft Technology MVI69-DFCM User Manual
Page 96

MVI69-DFCM ♦ CompactLogix or MicroLogix Platform
Reference
DF1 Interface Module
Page 96 of 117
ProSoft Technology, Inc.
November 3, 2008
Column
Parameter
Description
Parameter
8
Word Address
Word address where to start the write operation.
P1
9 to 11
Not Used
These fields are not used by the command. Values
entered in these columns will be ignored.
P2 to P4
This function sets or resets individual bits within a limited area of the PLC data
table. This function should work on the following devices: 1774-PLC, PLC-2,
PLC-3 and PLC-5.
Function Code #5 - Unprotected Write (Basic Command Set)
Column
Parameter
Description
Parameter
1
Enable/Type Word
0=Disabled, 1=Continuous and 2=Conditional.
2
Virtual Database Address
This parameter defines the database address of the first
data point to be associated with the command.
3
Poll Interval
Minimum time in tenths of a second to wait before
polling with this command.
4
Count
Number of data word values to be considered by the
function.
5
Swap Type Code
Swap type code for command: 0=None, 1=Swap words,
2=Swap words & bytes and 3=swap bytes in each word.
6
Node Address
Address of unit to reach on the data highway.
7
Function Code = 5
Unprotected Write Function
8
Word Address
Word address where to start the write operation.
P1
9 to 11
Not Used
These fields are not used by the command. Values
entered in these columns will be ignored.
P2 to P4
This function writes one or more words of data to the PLC memory. This function
should work on the following devices: 1774-PLC, PLC-2, PLC-3, PLC-5, SLC
500, SLC 5/03, SLC 5/04 and MicroLogix 1000.
Function Code #100 - Word Range Write (PLC-5 Command) (Binary Address)
Column
Parameter
Description
Parameter
1
Enable/Type Word
0=Disabled, 1=Continuous and 2=Conditional.
2
Virtual Database Address
This parameter defines the database address of the first
data point to be associated with the command.
3
Poll Interval
Minimum time in tenths of a second to wait before
polling with this command.
4
Count
Number of data word values to be considered by the
function.
5
Swap Type Code
Swap type code for command: 0=None, 1=Swap words,
2=Swap words & bytes and 3=swap bytes in each word.
6
Node Address
Address of unit to reach on the data highway.
7
Function Code = 100
Word Range Write Command.
8
File Number
PLC-5 file number to be associated with the command.
If a value of -1 is entered for the parameter, the field will
not be used in the command, and the default file will be
used.
P1