5.1.1 General
Specifications
Single Slot - 1769 backplane compatible
The module is recognized as an Input/Output module and has access to
processor memory for data transfer between processor and module
Ladder Logic is used for data transfer between module and processor.
Sample ladder file included.
Configuration data obtained from configuration text file downloaded to
module. Sample configuration file included.
Supports all CompactLogix processors: L20/L23/L30/L31/L32/L35, L43 and
L45 (L43 and L45 supported with RSLogix 5000 v16.03 or later)
Also supports MicroLogix 1500 LRP
5.1.2 Hardware
Specifications
Specification Description
Dimensions
Standard 1769 Single-slot module
Current Load
800 mA max@ 5 VDC
Power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus)
Operating Temp.
0 to 60°C (32 to 140°F)
Storage Temp.
-40 to 85°C (-40 to 185°F)
Relative Humidity
5% to 95% (non-condensing)
LED Indicators
Battery and Module Status
Application Status
Serial Port Activity
CFG Port Activity
CFG Port (CFG)
RJ45 (DB-9F with supplied cable)
RS-232 only
No hardware handshaking
App Ports (P1,P2) (Serial modules)
RS-232, RS-485 or RS-422 (jumper selectable)
RJ45 (DB-9F with supplied cable)
RS-232 handshaking configurable
500V Optical isolation from backplane
Shipped with Unit
RJ45 to DB-9M cables for each port
6-foot RS-232 configuration Cable
5.1.3 Functional
Specifications
DF1 ports
Full and half duplex modes supported
CRC and BCC error checking
Full hardware handshaking control provides radio, modem and multi-drop
support
User-definable module memory usage, supporting the storage and transfer of
up to 4000 registers to/from the control processor
125 word read and write command lengths supported
Floating point data movement supported