beautypg.com

ProSoft Technology MVI69-MCM User Manual

Page 149

background image

MVI69-MCM ♦ CompactLogix or MicroLogix Platform

Reference

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 149 of 167

March 22, 2011

5.7.3 RS-422

The RS-422 interface requires a single four or five wire cable. The Common

connection is optional, depending on the RS-422 network devices used. The

cable required for this interface is shown below:

5.7.4 RS-485 Application Port(s)

The RS-485 interface requires a single two or three wire cable. The Common

connection is optional, depending on the RS-485 network devices used. The

cable required for this interface is shown below:

Note: Terminating resistors are generally not required on the RS-485 network, unless you are
experiencing communication problems that can be attributed to signal echoes or reflections. In
these cases, installing a 120-ohm terminating resistor between pins 1 and 8 on the module
connector end of the RS-485 line may improve communication quality.

RS-485 and RS-422 Tip
If communication in the RS-422 or RS-485 mode does not work at first, despite

all attempts, try switching termination polarities. Some manufacturers interpret +

and -, or A and B, polarities differently.