ProSoft Technology MVI69-MCM User Manual
Page 137
MVI69-MCM ♦ CompactLogix or MicroLogix Platform
Reference
Modbus Communication Module
User Manual
ProSoft Technology, Inc.
Page 137 of 167
March 22, 2011
Response
The addressed Slave responds with its address and the function code, followed
by the information field. The information field contains 1 byte describing the
quantity of data bytes to be returned. The contents of the registers requested
(DATA) are two bytes each, with the binary content right justified within each pair
of characters. The first byte includes the high order bits and the second, the low
order bits.
Because the Slave interface device is normally serviced at the end of the
controller's scan, the data will reflect the register content at the end of the scan.
Some Slaves will limit the quantity of register content provided each scan; thus
for large register quantities, multiple transmissions will be made using register
content from sequential scans.
In the example below, the registers 40108 to 40110 have the decimal contents
555, 0, and 100 respectively.
Adr Func
ByteCnt
Hi Data
Lo Data
Hi Data
Lo Data
Hi Data
Lo Data
Error Check Field
11
03
06
02
2B
00
00
00
64
CRC
5.6.5 Read Input Registers (Function Code 04)
Query
Function code 04 obtains the contents of the controller's input registers at
addresses 3xxxx. These locations receive their values from devices connected to
the I/O structure and can only be referenced, not altered from within the
controller, The addressing allows up to 125 registers to be obtained at each
request; however, the specific Slave device may have restrictions that lower this
maximum quantity. The registers are numbered for zero (30001 = zero, 30002 =
one, and so on). Broadcast mode is not allowed.
The example below requests the contents of register 3009 in Slave number 11.
Adr Func Data Start Reg Hi Data Start Reg Lo Data #of Regs Hi
Data #of Regs Lo
Error Check Field
11
04
00
08
00
01
CRC