5.5.2 Slave Status Blocks
Slave status blocks send status information of each slave device on a Master
port. Slaves attached to the Master port can have one of the following states:
State
Description
0
The slave is inactive and not defined in the command list for the Master port.
1
The slave is actively being polled or controlled by the Master port
2
The Master port has failed to communicate with the slave device. Communications
with the slave is suspended for a user defined period based on the scanning of the
command list.
3
Communications with the slave has been disabled by the ladder logic. No
communication will occur with the slave until this state is cleared by the ladder logic.
Slaves are defined to the system when the module initializes the Master
command list. Each slave defined will be set to a state of one in this initial step. If
the Master port fails to communicate with a slave device (retry count expired on a
command), the Master will set the state of the slave to a value of 2 in the status
table. This suspends communication with the slave device for a user specified
scan count (E
RROR
D
ELAY
C
OUNT
parameter in the configuration file). Each time
a command in the list is scanned that has the address of a suspended slave, the
delay counter value will be decremented. When the value reaches zero, the slave
state will be set to one.
In order to read the slave status table, refer to the sample ladder logic. The
ladder logic must send a special block to the module to request the data. Each
port has a specific set of blocks to request the data as follows:
Block ID
Description
3002
Request status for slaves 0 to 59 for Port 1
3003
Request status for slaves 60 to 119 for Port 1
3004
Request status for slaves 120 to 179 for Port 1
3005
Request status for slaves 180 to 239 for Port 1
3006
Request status for slaves 240 to 255 for Port 1
3102
Request status for slaves 0 to 59 for Port 2
3103
Request status for slaves 60 to 119 for Port 2
3104
Request status for slaves 120 to 179 for Port 2
3105
Request status for slaves 180 to 239 for Port 2
3106
Request status for slaves 240 to 255 for Port 2
The following topics describe the format of these blocks:
Write Block - Request Slave Status
Offset
Description
Length (words)
0
3002 to 3006 or 3102 to 3106
1
1 to n
Spare
n
n=60, 120, or 240 depending on the Block Transfer Size parameter (refer to the configuration file).
The module will recognize the request by receiving the special write block code
and respond with a read block with the following format: