beautypg.com

ProSoft Technology MVI69-DNPSNET User Manual

Page 42

background image

MVI69-DNPSNET ♦ CompactLogix or MicroLogix Platform

Ladder Logic

Distributed Network Protocol Interface Module

Page 42 of 119

ProSoft Technology, Inc.

November 3, 2008

This action opens the following dialog box:

2 Select the 1769-Module (Generic 1769 Module) from the list and click OK.

3 Enter the Name, Description and Slot options for your application, using the

values in the illustration above. You must select the Comm Format as Data -
INT
in the dialog box, otherwise the module will not communicate over the
backplane of the CompactLogix rack.

4 Configure the Connection Parameters to match to the Block Transfer Size

parameter in the configuration file. Use the values in the table corresponding
with the block transfer size you configured.

Block Transfer Size = 60

Field Recommended

Value

Type

1769-MODULE Generic 1769 Module

Parent Local

Name MVI69

Description

MVI69 Application Module

Comm Format

Data - INT

This manual is related to the following products: