Device profile, Device, Profile – ProSoft Technology MVI69-DNPSNET User Manual
Page 100: 7 device profile
MVI69-DNPSNET ♦ CompactLogix or MicroLogix Platform
Reference
Distributed Network Protocol Interface Module
Page 100 of 119
ProSoft Technology, Inc.
November 3, 2008
5.7 Device
Profile
DNP V3.00
DEVICE PROFILE DOCUMENT
Vendor Name:
ProSoft Technology, Inc.
Device Name:
MVI69-DNPSNET (VERSION 1.00)
Highest DNP Level Supported :
Device Function:
For Request: L2
For Responses: L2
Slave (TCP/IP Server (Data Provider))
Notable objects, functions, and/or qualifiers supported in addition to the highest DNP level stated above (see attached
table for complete list):
Definition of selected IIN bits: Supports both TCP and UDP protocols as specified in the recommendation document.
Supports new function 24 and object 50 variation 3 for time synchronization. Supports list of valid IP addresses for
clients to connect (may be disabled by user). Setting of IP list secure. Supports receipt of multiple messages in a single
network packet.
The following features are configurable on the module: Time sync before events are generated and default analog input
events, Obj32V4 or O32V2, select option.
Counter Freeze with reset will not zero values in the processor. Therefore, this function should not be utilized.
Module will not generate events until Restart IIN bit is cleared by DNP master.
Maximum Data Link Frame Size (octets):
Maximum Application Fragment Size (octets):
Transmitted : 292
Transmitted : 2048
Received : 292
Received : 2048
Maximum Data Link Re-tries:
Maximum Application Layer Re-tries:
Configurable
None
Requires Data Link Layer Confirmation:
Always set to Never as defined in recommendation
Requires Application Layer Confirmation:
When reporting Event Data as a slave unit
Time-outs while waiting for:
Data Link Confirm
: NA
Complete Application Fragment
: Configurable at module start-up
Application Confirm
: Configurable at module start-up (1 to 65535 mSec)
Complete Application Response
: None
Sends/Executes Control Operations:
WRITE Binary Outputs
: Never
SELECT/OPERATE :
Always
DIRECT OPERATE
: Always
DIRECT OPERATE-NO ACK
: Always
Count > 1
: Always (1 to 65535)
Pulse On
: Always
Pulse Off
: Always
Latch On
: Always
Latch Off
: Always
Queue :
Never
Clear Queue
: Never