ProSoft Technology MVI69-DNPSNET User Manual
Page 31

Configuring the MVI69-DNPSNET Module
MVI69-DNPSNET ♦ CompactLogix or MicroLogix Platform
Distributed Network Protocol Interface Module
ProSoft Technology, Inc.
Page 31 of 119
November 3, 2008
2.3.24 BI with Flag
Yes or No
This parameter determines which variation will be returned for object 1 when the
master requests variation 0. If the parameter is set to N, variation 1 will be
returned. If the parameter is set to Y, variation 2 will be returned.
Note: Flag will always be set for Online and cannot be changed through by the PLC or user
program. Only the default variation returned by the module will be affected by changing this
parameter.
2.3.25 BI Events Without Time
Yes or No
This parameter determines if the binary input events generated by the module
will include the date and time of the event. If the parameter is set to Yes, the
default is set to no time data. If the parameter is set to No, the default object will
include the time of the event.
2.3.26 AI with Flag
Yes or No
This parameter determines which variation will be returned for object 30 when
the master requests variation 0. If the parameter is set to N, variation 4 will be
returned. If the parameter is set to Y, variation 2 will be returned.
Note: Flag will always be set for Online and cannot be changed through by the PLC or user
program. Only the default variation returned by the module will be affected by changing this
parameter.
2.3.27 AI Events with Time
Yes or No
This parameter determines if the analog input events generated by the module
will include the date and time of the event. If the parameter is set to N, the default
is set to no time data. If the parameter is set to Y, the default object will include
the time of the event.
2.3.28 BO Without Flag
Yes or No
This parameter determines which variation will be returned for object 10 when
the master requests variation 0. If the parameter is set to N, variation 2 will be
returned. If the parameter is set to Y, variation 1 will be returned.