MVI69L-MBTCP Configuration
Communication Module
User Manual
ProSoft Technology, Inc.
Page 49 of 152
January 6, 2014
3.2
Module Configuration Parameters
3.2.1 Module
This section contains general module configuration parameters, including
database allocation and backplane transfer options.
Parameter
Value
Description
Module Name
ASCII
characters
(max. 80)
Assigns a name to the module that can be viewed using
the configuration/debug port. Use this parameter to
identify the module and the configuration file.
Failure Flag Count
0 to 65535
Specifies the number of consecutive backplane transfer
failures that can occur before Modbus communications
should be halted.
Error/Status Pointer
-1 to 239
Starting register location in virtual Modbus database for
the error/status table. If a value of -1 is entered, the
error/status data will not be placed in the database. All
other valid values determine the starting location of the
data. This data area includes the module version
information and all server error/status data. Refer to
General Status (page 88) for more information.
Initialize Input Image
Yes or No
This parameter is used to determine if the input image
data, the module’s Read Register Data values, should be
initialized with Read Register Data values from the
processor. If the value is set to No, the Read Register
Data values in the module will be set to 0 upon