Func Code - Tells the Client to read the register values from the Server. FC3.
Addr in Dev - Tells the Client where in the Server's database to obtain the data.
In the above example, the Client's Modbus command to transmit inside the
Modbus packet will be as follows.
Server address Function Code Address in Device Reg count
DEC
01
3
6100
2
HEX
01
03
17 D4
00 02
In the above example the (Enron/Daniel supporting) Server's Modbus command
to transmit inside the Modbus packet will be as follows.
Server address Function Code Byte Count
Data
DEC
01
3
8
32.75 275.69
HEX
01
03
08
00 00 42 03 D8 52 43 89
In the above example the (a NON-Enron/Daniel supporting) Server's Modbus
command that will be transmitted inside the Modbus packet will be as follows.
Server address Function Code Byte Count
Data
DEC
01
3
4
32.75
HEX
01
03
04
00 00 42 03