Offset
Description
39
Encapsulated Modbus TCP/IP request count: This counter increments each time
an Encapsulated Modbus TCP/IP (Service Port 2000) request is received from a
remote Modbus TCP/IP client
40
Encapsulated Modbus TCP/IP response count: This counter increments each time
an Encapsulated Modbus TCP/IP (Service Port 2000) response is sent back to a
remote Modbus TCP/IP client command
41
Encapsulated Modbus TCP/IP error sent: This counter increments each time an
error is sent from the server to the remote Modbus TCP/IP client
42
Encapsulated Modbus TCP/IP error received: This counter increments each time
an error is received from a remote Modbus TCP/IP client
43
Modbus MBAP request count: This counter increments each time an MBAP
(Service Port 502) request is received from a remote Modbus TCP/IP client
44
Modbus MBAP response count: This counter increments each time an MBAP
(Service Port 502) response is sent back to a remote Modbus TCP/IP client
command
45
Modbus MBAP error sent: This counter increments each time an error is sent from
the server to the remote MBAP Modbus TCP/IP client
46
Modbus MBAP error received: This counter increments each time an error is
received from a remote MBAP Modbus TCP/IP client
47 to 239
Spare