Communication error codes – ProSoft Technology MVI69L-MBTCP User Manual
Page 103

MVI69L-MBTCP ♦ CompactLogix Platform
Diagnostics and Troubleshooting
Communication Module
User Manual
ProSoft Technology, Inc.
Page 103 of 152
January 6, 2014
6.5
Communication Error Codes
Standard Modbus Protocol Exception Code Errors
Code
Description
1
Illegal Function Code
2
Illegal Data Address
3
Illegal Data Value
4
Failure in Associated Device
5
Acknowledge
6
Busy, Rejected Message
Module Communication Error Codes
Code
Description
-1
CTS modem control line not set before transmit
-2
Timeout while transmitting message
-11
Timeout waiting for response after request
253
Incorrect slave address in response
254
Incorrect function code in response
255
Invalid CRC/LRC value in response
Command List Entry Errors
Code
Description
-41
Invalid enable code
-42
Internal address > maximum address
-43
Invalid node address (< 0 or > 255)
-44
Count parameter set to 0
-45
Invalid function code
-46
Invalid swap code
MBTCP Client-Specific Errors
Code
Description
-33
Failed to connect to server specified in command
-36
MBTCP command response timeout
-37
TCP/IP connection ended before session finished
Note: If an error code is reported that is not listed above, check with the documentation of the end
device. Device-specific error codes can be produced by the end device.