Set module time using received time block, Pass module time to processor block – ProSoft Technology MVI69L-MBTCP User Manual
Page 145

MVI69L-MBTCP ♦ CompactLogix Platform
Reference
Communication Module
User Manual
ProSoft Technology, Inc.
Page 145 of 152
January 6, 2014
7.4.19 Set Module Time Using Received Time Block
Block 9972: Set Module Time Using Received Time Block
This block will use the time information of the processor to set the module time.
Block 9972: Request from Processor to Module
Offset
Description
0
Block ID 9972
1
Year (0-9999)
2
Month (1-12)
3
Day (1-31)
4
Hour (0-23)
5
Minutes (0-59)
6
Seconds (0-59)
7
Milliseconds (0-999)
8 to 239
Spare
Block 9972: Response from Module to Processor
Offset
Description
0
Block ID 9972
1
Write Block ID
2
Return code 0=OK, -1=error
3 to 239
Spare
7.4.20 Pass Module Time to Processor Block
Block 9973: Pass Module Time to Processor Block
This block will use the time information of the module to set the processor time.
Block 9973: Request from Processor to Module
Offset
Description
0
Block ID 9973
1 to 239
Spare
Block 9973: Response from Module to Processor