Installing the module in the rack – ProSoft Technology MVI69L-MBTCP User Manual
Page 13
MVI69L-MBTCP ♦ CompactLogix Platform
Start Here
Communication Module
User Manual
ProSoft Technology, Inc.
Page 13 of 152
January 6, 2014
1.5
Installing the Module in the Rack
Make sure the processor and power supply are installed and configured before
installing the MVI69L-MBTCP module. Refer to the Rockwell Automation product
documentation for installation instructions.
Warning: Please follow all safety instructions when installing this or any other electronic devices.
Failure to follow safety procedures could result in damage to hardware or data, or even serious
injury or death to personnel. Refer to the documentation for each device to be connected to verify
that suitable safety procedures are in place before installing or servicing the device.
After the jumper placements are verified, insert the MVI69L-MBTCP into the rack.
Use the same technique recommended by Rockwell Automation to remove and
install CompactLogix modules.
Warning: This module is not hot-swappable! Always remove power from the rack before
inserting or removing this module, or damage may result to the module, the processor, or other
connected devices.
1 Align the module using the upper and lower tongue-and-groove slots with the
adjacent module and slide forward in the direction of the arrow.