Flow Meter FC01-LQ

Flow Meter FC01-LQ

Configuration

31

Configuration

31

Enter the following characteristics when selecting a CSP monitoring head with sensor adapter TP-..:

1. SENSOR CODE C value

characteristics range: 700 … 1300

2. SENSOR CODE T value

characteristics range: 01 … 99

The internal diameter of the sensor adapter is selcted in menu option TYPE SELECT.

Available sizes are:

TP01 (1/2 in)

• TP04 (1 1/4 in)

TP02 (3/4 in)

• TP05 (1 1/2 in)

TP03 (1 in)

• TP06 (2 in)

5.3 Limit switch combinations (menu option: LIMIT SWITCHES)

The FC01-LQ comprises two limit switches (LS1 and LS2) which are assigned to the physical
quantity/quantities to be monitored in submenu LIMIT SWITCHES.

The following combinations are available:

LS1

F and LS2 F

limit switch 1

flow rate

limit switch 2

flow rate

• LS1

T and LS2 T

limit switch 1

medium temperature

limit switch 2

medium temperature

LS1

F and LS2 T

limit switch 1

flow rate

limit switch 2

medium temperature

• LS1

T and LS2 F

limit switch 1

medium temperature

limit switch 2

flow rate

Mode of operation, limit value and hysteresis of the limit switches are set in menu PARAMETER

SELECTION.

Caution!

Menu option LIMIT SWITCHES may influence data in the parameter selection menu (see
para. 5.12, Quitting the configuration menu).

Enter the following characteristics when selecting a CSP monitoring head with sensor adapter TP-..:

1. SENSOR CODE C value

characteristics range: 700 … 1300

2. SENSOR CODE T value

characteristics range: 01 … 99

The internal diameter of the sensor adapter is selcted in menu option TYPE SELECT.

Available sizes are:

TP01 (1/2 in)

• TP04 (1 1/4 in)

TP02 (3/4 in)

• TP05 (1 1/2 in)

TP03 (1 in)

• TP06 (2 in)

5.3 Limit switch combinations (menu option: LIMIT SWITCHES)

The FC01-LQ comprises two limit switches (LS1 and LS2) which are assigned to the physical
quantity/quantities to be monitored in submenu LIMIT SWITCHES.

The following combinations are available:

LS1

F and LS2 F

limit switch 1

flow rate

limit switch 2

flow rate

• LS1

T and LS2 T

limit switch 1

medium temperature

limit switch 2

medium temperature

LS1

F and LS2 T

limit switch 1

flow rate

limit switch 2

medium temperature

• LS1

T and LS2 F

limit switch 1

medium temperature

limit switch 2

flow rate

Mode of operation, limit value and hysteresis of the limit switches are set in menu PARAMETER

SELECTION.

Caution!

Menu option LIMIT SWITCHES may influence data in the parameter selection menu (see
para. 5.12, Quitting the configuration menu).