beautypg.com

Parallel connection of three rcw power supplies – KEPCO RCW 350W Series User Manual

Page 13

background image

RCW350W 120607

11

FIGURE 8 PARALLEL CONNECTION OF THREE RCW POWER SUPPLIES

NOTES

1) Maintain the connecting links between the (+) M and (+) S terminals and between the (–) M and (–) S terminal.
2) Set voltage of unit 1 to the desired voltage at the load.
3) With three RCW 350W units in parallel the output voltage of each Power Supply must be set to less than 2% of each other
4) When the Current Balance function is used with the Remote ON/OFF function, connect all the (+) RC terminals together and all

the (–) RC terminals together.

5) Use the same length and wire size for load connecting wires from the (+) and (–) terminal screws of each RCW 350W Power

Supply to the load terminals

6) Use the same length and wire size for twisted pair Sensing wires from the (+) S and (–) S terminals of each RCW 350W power

Supply to the load terminals