Thermo Pride Gas/Propane Furnace Premiere Series 2-Stage CHX3 User Manual
Page 8

All installations and services must be performed by qualified service personnel.
2
CDX3 SERIES
MODEL NO.
CDX3-75
CDX3-100
CDX3-125
BTU/HR INPUT (High fire / Low fire)
75,000 / 56,250 100,000 / 75,000 125,000 / 93,750
BTU/HR OUTPUT (High fire / Low fire)
71,000 / 52,000
94,000 / 69,000
116,000 / 87,000
HEIGHT OF CASING
46-1/4”
46-1/4”
46-1/4”
WIDTH OF CASING
17”
21”
24”
DEPTH OF CASING
27-1/2”
27-1/2”
27-1/2”
WARM AIR OUTLET
15 x 18
19 x 18
22 x 18
RETURN AIR INLET
15 x 22
19 x 22
22 x 22
DIA. OF FLUE
2”
3”
3”
DIA. OF COMBUSTION
AIR INTAKE
2”
3”
3”
CFM from .2” & .5” w.c.
EXTERNAL STATIC PRESSURE
COOLING
COOLING
COOLING
@COOLING TAP A
1000
1200
1400
@COOLING TAP B
800
1000
1200
@COOLING TAP C
1200
1400
1600
@COOLING TAP D
1400
1600
2000
HEATING
HEATING
HEATING
@HEATING TAP C (High fire / Low fire)
1012 / 826
1340 / 1094
1673 / 1366
TEMPERATURE RISE
65 / 60
65 / 60
65 / 60
BLOWER MOTOR HP
.5
.75
1
POWER CHOKES
-
2.65Mh
2.1Mh
LARGEST RECOMMEDED
AIR CONDITIONER
3.5 Ton
4 Ton
5 Ton
SIZE OF FILTERS
21-3/4” x 14”(2)
21-3/4” x 14”(2)
21-3/4” x 14”(2)
NOTES:
1. BTU output based on annual fuel utilization efficiency rated by manufacturer.
2. On all outlet and inlet dimensions, the first dimension is width.
3. To permit largest recommended air conditioning (at .5 static pressure), selection of the highest motor
speed is required.
4. Electrical characteristics at 115 volts, 60 Hz., 1 phase (less than 15 amps. for all models).
5. All specifications are subject to change without notice.