All installations and services must be performed by qualified service personnel.

36

FLAME MUST BE DETECTED

WITHIN 4 SECONDS IF

FLAME IS DETECTED, THE

DELAY-TO-FAN-ON TIME

BEGINS (45 SECONDS)

THE RETRY SEQUENCE

PROVIDES A 60 SECOND

WAIT BEFORE IGNITION

RETRY. RETRY IS

ATTEMPTED WITH A

DIFFERENT VOLTAGE

SETTING.

IF NOT

IF SO

AFTER IGNITOR WARM-UP,

THE 36J54 GAS VALVE IS
ENERGIZED TO OPEN ON

LOW FIRE SETTING

IF FLAME IS NOT DETECTED, THE

GAS VALVE IS DE-ENERGIZED,

THE IGNITOR IS TURNED OFF AND

THE 50V51-843 CONTROL GOES

INTO "RETRY" SEQUENCE

IF IGNITION ATTEMPT IS

UNSUCCESSFUL, ONE MORE

RETRY WILL BE MADE

BEFORE THE 50V51-843

GOES INTO SYSTEM LOCKOUT

IF FLAME IS DETECTED, THEN LOST,

THE 50V51-843 WILL REPEAT THE

INITIAL IGNITION SEQUENCE FOR A

TOTAL OF TEN RECYCLES. AFTER

TEN UNSUCCESSFUL RECYCLE

ATTEMPTS, THE CONTROL WILL

GO INTO SYSTEM LOCKOUT.