Thermo Pride Gas/Propane Furnace Premiere Series 2-Stage CHX3 User Manual
Page 18

All installations and services must be performed by qualified service personnel.
12
b. The bottom edge of the vent termination elbow must be installed at least 12-inches above the
outlet of intake termination elbow.
c. The horizontal distance between the inlet and exhaust terminations should be minimized,
when possible, and should never exceed 24-inches.
d. The vent and intake systems should utilize the same numbers of elbows and approximately
the same length of straight pipe to reach the outside termination.
Figure 3: Typical Relative Locations of Direct Vent Terminations When Sidewall Venting.
3. Exhaust Vent Terminal Location Clearance Requirements
a. The vent terminal shall be located at least 3-feet above any forced air inlet located within 10-
feet. Refer to Figure 4 for a depiction of the required minimum clearances between vent
terminations and building features according to the National Fuel Gas Code (NFGC).
b. The vent terminal shall be at least 12-inches below, 12-inches horizontally from, or 12-inches
above, any door, window, or gravity air inlet into a building. The bottom of the vent terminal
shall be located at least 12-inches above grade.
c. The vent terminal shall not be located:
• over public walkways or over an area where wetting of surfaces by condensate, or water
vapor, could create a nuisance or hazard,
• near soffit vents, crawl space vents, or other areas where condensate or water vapor
could create a nuisance, hazard, or cause property damage, and
• where wetting of components by condensate, or water vapor, could be detrimental to the
operation of pressure regulators, relief valves, or any other equipment.
d. The vent terminal shall be installed a minimum of 14-inches from any obstruction and 3-feet
from an inside corner of an L-shaped structure.