All installations and services must be performed by qualified service personnel.

34

Modifications to ECM blower speed settings are done using the S3 and S4 dip switch controls. Thermo
Pride two-stage furnaces are factory shipped at the CFM settings listed below in Table 4C.

2-Stage Blower Settings (from factory)

Table 4C

Unit

Control Board

Dip Switch

Settings

Heating

CFM

(low fire)

Heating

CFM

(high fire)

Constant Fan

CFM

Cooling

CFM

CDX3-75

SW3 1-4 Off
SW4 1-3 Off

SW4 4 On

885

1012

500

1000

CHX3-75

SW3 1-4 Off
SW4 1-4 Off

760

931

500

1000

CDX3-100

SW3 1-4 Off
SW4 1-3 Off

SW4 4 On

1094

1340

600

1200

CHX3-100

SW3 1-4 Off
SW4 1-4 Off

1015

1243

600

1200

CDX3-125

SW3 1-4 Off
SW4 1-3 Off

SW4 4 On

1366

1673

700

1400

CHX3-125

SW3 1-4 Off
SW4 1-4 Off

1270

1556

700

1400


For adjustments to the Cooling CFM settings, as well as all additional CFM changes, please reference the
dip switch tables listed in the ECM operation manual. (Included with every furnace.)


5. DE-HUMIDIFICATION

The ECM motor in conjunction with the W/R 50V51-843 has a feature to enhance de-humidification in the
cooling mode. In the dehumidify mode the indoor blower motor (ECM) reduces CFM. By reducing airflow
the indoor coil runs colder and thus extracts more moisture from the air.

The W/R 50V51-843 is shipped from the factory with dipswitch S5-2 set to on for system that do not have
a dehumidification connection from the thermostat. For systems using a thermostat that provides
dehumidification option move dip switch S5-2 to “OFF”. With the S5-2 switch in the “OFF” position the air
conditioning fan speed will be reduced 30% from the normal CFM setting when the humidity in the home is
higher than the set point of the dehumidistat.


6. FIELD WIRING AND REPLACING WIRING

Field wiring between the furnace and devices not attached to the furnace shall conform with the
temperature limitation for Type T wire[63°F rise (35°C)] when installed in accordance with the
manufacturer’s instructions. If any of the original factory supplied furnace wiring is replaced or a separate
device other than the thermostat is wired internal to the unit 105

°C thermoplastic or equivalent wire must

be used.