All installations and services must be performed by qualified service personnel.

50

IS INDUCER RUNNING

ON LOW SPEED?

DOES THE HOT

SURFACE IGNITOR

ENERGIZE AND GLOW?

CHECK WIRING TO HOT
SURFACE IGNITOR AND

IF OK, REPLACE HOT

SURFACE IGNITOR

ASSEMBLY

AFTER HOT SURFACE

IGNITOR WARM-UP,

DOES GAS VALVE OPEN?

NO

NO

NO

NO

YES

YES

YES

CHECK CONTACTS ON LOW

FIRE PRESSURE SWITCH

AND FOR BLOCKAGE IN FLUE.

IF OK, REPLACE DUAL

PRESSURE SWITCH.

IS THE HIGH LIMIT,

ROLL-OUT LIMIT, AND

AUX LIMIT ON

(CDX MODELS)

SWITCHES CLOSED?

NO

YES

YES

IF HIGH LIMIT OR

AUX LIMIT OPEN CHECK

FOR RESTRICTED

FILTERS OR DUCT WORK

IF ROLL-OUT SWITCH

OPEN INSPECT FLUE FOR

RESTRICTIONS.

NO

CHECK WIRING TO GAS

VALVE AND IF OK,

REPLACE GAS VALVE.

IS COLLECTOR BOX

PRESSURE SWITCH CLOSED?

YES

YES

CHECK DRAIN FOR

BLOCKAGE WATER
TRAPPED IN HOSE,

REPLACE SWITCH.

NO

NO

AFTER GAS VALVE

OPENS, DO THE

BURNERS IGNITE?

YES

OK

CHECK FOR PROPER LINE

AND MANIFOLD PRESSURE.

REFERENCE GAS PRESSURE

CHART PAGE 31.

IS THERE VOLTAGE ACROSS

HOT SURFACE IGNITOR

TERMINALS "IGN" & "IGN N"

AT THE 50V51-843 CONTROL

AFTER 17 SECOND PREPURGE?

REPLACE THE

50V51-843 CONTROL.

CHECK ACROSS "MVL" AND

"MV COM" TERMINALS ON

50V51-843 CONTROL FOR 24

VOLTS DURING THE 4 SECOND

FLAME PROVING PERIOD

AFTER IGNITOR WARM-UP.

IS THERE 24 VOLTS?

REPLACE THE

50V51-843 CONTROL.