beautypg.com

Thermo Pride Gas/Propane Furnace Premiere Series 2-Stage CHX3 User Manual

Page 57

background image

All installations and services must be performed by qualified service personnel.

51

IS IGNITOR

POSITIONED CORRECTLY?

REPOSITION TO

CORRECT LOCATION

CHECK AND CLEAN BURNERS

DO BURNERS STAY
LIT PAST PROOF OF

FLAME CHECK?

IS W2 ENERGIZED?

DOES INDUCER

GO TO

HIGH SPEED?

IS THERE LINE

VOLTAGE ACROSS

INDUCER POWER

TERMINALS "IND HI"

TO "IND N"?

REPLACE

THE 50V61-143

CONTROL.

CHECK CONNECTIONS

TO INDUCER. IF OK,

REPLACE INDUCER.

DOES BURNER

STEP TO HIGH FIRE?

IS THE HIGH FIRE

PRESSURE SWITCH

CLOSED?

YES

NO

YES

NO

NO

NO

YES

YES

YES

YES

YES

NO

NO

NO

OK

CHECK FLAME PROB2

AND WIRE AND CHECK

POLARITY ON INCOMING

POWER AND GROUND

CHECK

CONTACTS

IN HIGH

FIRE SWITCH

AND FOR

BLOCKAGE IN

FLUE. IF OK,

REPLACE DUAL

PRESSURE

SWITCH.

CHECK FOR PROPER LINE

AND MANIFOLD PRESSURE

REFERENCE GAS

PRESSURE CHART PAGE 31.