Thermo Pride Gas/Propane Furnace Premiere Series 2-Stage CHX3 User Manual

Page 22

background image

All installations and services must be performed by qualified service personnel.

16

Install these optional kits according to the instructions provided with each kit. The location and
clearance requirements are identical to those of the standard vent terminations described in this
manual.

Figure 6: Optional Direct Vent Kits for the CHX3 / CDX3 Model Series of Furnaces


G. Connecting The Furnace To Roof Exhaust / Intake Terminations

If it is not desirable, or feasible, to vent the furnace through a sidewall, it may be vertically vented
through the roof. Installation shall conform to the following guidelines, which are illustrated in
Figure 6A, below.

1. The outlet of the exhaust vent and the inlet of the combustion air intake, i.e. the terminations,

shall be a minimum of 12-inches above highest anticipated snow level.


2. The exhaust vent outlet must be installed a minimum of 12-inches above the air intake inlet.

3. Where exposed to prevailing winds, the combustion air intake shall be installed upwind of the

vent outlet.

4. The exhaust vent and combustion air intake can be a minimum of 3-inches and a maximum

of 24 inches apart.


NOTICE: When the vent termination is installed correctly, a draft should NOT be present in
the system during the furnace off-cycle.

Figure 6A: Typical Rooftop Vent and Air Intake Termination Construction Details

370191

SIDE WALL VENT KIT

VERTICAL

HORIZONTAL

AOPS7488 / AOPS7489

CONENTRIC VENT KIT