beautypg.com

Checking gas supply pressure, Pilot flame adjustment – Thermo Pride Thermo Pace Downflow/Horizontal Furnace (CSA) User Manual

Page 25

background image

Installer’s Information Manual

Page 25

SECTION 12. GAS SUPPLY
PRESSURE AND PILOT
ADJUSTMENT

You will need a 0 to 15 inch water manometer with 0.1 inch
resolution and a 1/8" NPT manual shut-off valve to measure
actual gas pressure.

CHECKING GAS SUPPLY PRESSURE

1. Turn off gas at equipment shut-off valve in gas supply

line just ahead of fu rnace.

2. Remove three screws holding burner access panel in

place. Remove burner access panel.

3. Remove inlet pressure plug from gas control. See

Figure 24.

4. Install 1/8" NPT manual shut-off valve in hole vacated

by plug. Make sure valve is in off position.

5. Attach manometer to 1/8" NPT manual shut-off valve

just installed.

6. Slowly open equipment shut-off valve in gas supply line

just ahead of fu rnace.

7. Slowly open 1/8" NPT manual shut-off valve leading to

manometer.

8. Turn on all gas appliances attached to gas supply line.

9. With furnace operating, read gas supply pressure on

manometer.

??

Natural gas supply pressure must be between 5
and 7 inches W.C.

??

Propane gas (LP) supply pressure must be
between 11 and 13 inches W.C.

10. If gas supply pressure is not within these limits, call gas

supplier. Tu rn off all gas appliances attached to gas
supply line.

11. Shut off furnace.

12. Turn off gas at equipment shut-off valve in gas supply

line just ahead of furnace. Remove shut-off valve from
gas -control inlet pressure tap. Install pressure tap
plug. Turn on gas.

13. Replace burner access panel using three screws

removed in step 2.

PILOT FLAME ADJUSTMENT

Before adjusting pilot flame, confirm that gas supply
pressure is correct, as explained above.

NOTE: Pilot flame adjustment was checked at the factory
and should not require adjustment. However; pilot
adjustment is possible if necessary.

1. Remove three screws holding burner access panel in

place. Remove burner access panel.

2. Start furnace following "Operating Instructions" on front

door.

3. Pilot flame should cover 1/2 inch of tip of flame sensor

as shown in Figure 29.

4. If you need to adjust pilot flame, remove pilot-

adjustment cover screw on gas control. Save cover
screw for re-installation. Tu rn inner adjustment screw
clockwise to decrease pilot flame; counter-clockwise to
increase pilot flame. Install cover screw and tighten to
torque of 5 inch-pounds to prevent gas leakage.

Figure 29. Pilot Flame Adjustment.

5. Check pilot-adjustment cover screw and gas -control

inlet-pressure-tap plug for gas leaks. Use a
commercial soap solution made for leak detection.

6. Replace burner access panel using three screws

removed in step 1.

SECTION 13. MANIFOLD
PRESSURE ADJUSTMENT

You will need a 0 to 15 inch water manometer with 0.1 inch
resolution and a 1/8" NPT manual shut-off valve to measure
actual manifold pressure.

WARNING: Correct manifold pressure is

necessary for proper ignition and b urner operation. Failure
to accurately adjust pressure could cause heat exchanger
failure.

Check gas -supply pressure first. Follow instructions in
Section 12, "Gas Supply Pressure and Pilot Adjustment."

1. Turn off gas at equipment shut-off valve in gas supply

line just ahead of fu rnace.

2. Remove three screws holding burner access panel in

place. Remove burner access panel.

3. Remove plug from manifold pressure tap in gas

control. See Figure 24.

4. Install 1/8" NPT manual shut-off valve in hole vacated

by plug. Make sure shut-off valve is in off position.