ProSYS Version 8.xx - Supplementary Instructions

5

d.

Press

to confirm.

e.

Repeat the above steps for other BUS detectors.

2. Assign the iWISE BUS detectors to a Zone:

a.

From the main Engineer menu select [2] Zones > [1] One by One.

b.

Select the zone number that you want to assign the BUS detector.

Note:

If you defined a virtual BUS Zone Expander, select a zone number from the virtual zones (defined
by the BUS Zone expander).

c.

Define Partitions, Groups, Zone Type and Zone Sound.

d.

In the Termination category, select [5] BUS Zone followed by

.

e.

Select the BUS zone number to assign to the programmed zone. The type field
will be updated automatically when selecting the zone.

f.

Press

. The loop response category is not applicable to a BUS zone.

g.

Press

, assign a label and press

.

3. If you want to use the extra wired zone input on the iWISE BUS detector:

a.

Repeat steps a. – c. in step 2 above.

b.

In the Termination category, select the relevant BUS Zone input termination:
[07] BUS Zone Input N/C
[08] BUS Zone Input EOL
[09] BUS Zone Input DEOL
[10] BUS Zone Input N/O
[11] BUS Zone Input TEOL

c.

Press

. Select the BUS zone that the input zone belongs to. The Type field

will be updated automatically when selecting the zone.

d.

Press

. Define the loop response time.

e.

Press

, assign a label and press

.

4. Configure the iWISE BUS detector parameters:

a.

From the main Engineer menu select [2] Zones > [0] Miscellaneous > [3] BUS
Zone Parameters.

b.

Select the zone that the BUS Zone was assigned to and press

.

c.

Use the following tables to configure the parameters for the relevant iWISE BUS
detector.