Setting flow meter pulse inputs – Precision Digital PD941 User Manual
Page 30

ConsoliDator Multi-Channel Controller
Instruction Manual
30
Setting Flow Meter Pulse 
Inputs 
The Flow Meter menu is used to 
configure a flow meter pulse input. All 
pulse input screens offer the same 
options as described in this section. 
Options are configured individually for 
each pulse input. 
To access Flow Meter menu: Select a 
Flow Meter input from the Inputs 
window in the main setup menu. 
To enter parameters in this menu, use 
EDIT key, then use arrow keys to 
modify the entries. Press SAVE when 
complete. 
Flow Meter: 1
State:
Channel ID: Flow: 1 ENABLED
 K Factor: 1000.00 pls / GAL
Max Value: 50.00 GPM
K-Fac Fmt: 9999.99 GPM
Rate Fmt: 9999.99 GPM
Total Fmt: 9999.99 GAL
Units: GAL & GPM
Display: RATE
EDIT
EXIT
Display Parameters
Channel ID
Enter a name for the channel, which appears on the operation screens, 
and wherever else the channel is referenced. 
Max Value
Specify the rate or total maximum. When this level is reached, the 
channel's bargraph will appear completely filled. 
Rate Fmt:
Select a position for the rate display decimal point by shifting left or right 
(zero to five places.) 
Total Fmt
Select a position for the total display decimal point by shifting left or 
right (zero to five places.) 
Units
Select from any available unit combinations for flow.
Display
Set to display [RATE] or [TOTAL] based bargraphs during operation. 
This entry also determines whether assigned relay actions (other than 
Trigger Relay) are linked to rate or total values. The picture on page 43 
shows a typical screen when set to display total. 
Input Configuration Parameters
State
Enable or disable the input by selecting [ENABLED] or [OFF]. If a 
certain flow meter input is not going to be used, [OFF] must be 
selected. 
K Factor
Specify the conversion factor "K" in pulses per unit.
K-Fac Fmt
Select a position for the K Factor decimal point by shifting left or right 
(zero to five places.) 
