Setting flow meter pulse inputs – Precision Digital PD941 User Manual
Page 30
ConsoliDator Multi-Channel Controller
Instruction Manual
30
Setting Flow Meter Pulse
Inputs
The Flow Meter menu is used to
configure a flow meter pulse input. All
pulse input screens offer the same
options as described in this section.
Options are configured individually for
each pulse input.
To access Flow Meter menu: Select a
Flow Meter input from the Inputs
window in the main setup menu.
To enter parameters in this menu, use
EDIT key, then use arrow keys to
modify the entries. Press SAVE when
complete.
Flow Meter: 1
State:
Channel ID: Flow: 1 ENABLED
K Factor: 1000.00 pls / GAL
Max Value: 50.00 GPM
K-Fac Fmt: 9999.99 GPM
Rate Fmt: 9999.99 GPM
Total Fmt: 9999.99 GAL
Units: GAL & GPM
Display: RATE
EDIT
EXIT
Display Parameters
Channel ID
Enter a name for the channel, which appears on the operation screens,
and wherever else the channel is referenced.
Max Value
Specify the rate or total maximum. When this level is reached, the
channel's bargraph will appear completely filled.
Rate Fmt:
Select a position for the rate display decimal point by shifting left or right
(zero to five places.)
Total Fmt
Select a position for the total display decimal point by shifting left or
right (zero to five places.)
Units
Select from any available unit combinations for flow.
Display
Set to display [RATE] or [TOTAL] based bargraphs during operation.
This entry also determines whether assigned relay actions (other than
Trigger Relay) are linked to rate or total values. The picture on page 43
shows a typical screen when set to display total.
Input Configuration Parameters
State
Enable or disable the input by selecting [ENABLED] or [OFF]. If a
certain flow meter input is not going to be used, [OFF] must be
selected.
K Factor
Specify the conversion factor "K" in pulses per unit.
K-Fac Fmt
Select a position for the K Factor decimal point by shifting left or right
(zero to five places.)