Reset meter to factory defaults – Precision Digital PD6060 User Manual
Page 88
Model PD6060 Dual-Input Process Meter
Instruction Manual
88
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to
determine what’s happening, it might be better to start the setup
process from the factory defaults.
Instructions to load factory defaults:
1. Enter
the
Advanced
Features menu. See Advanced Features
Menu
, page 66.
2. Press Up arrow to go to Diagnostics menu
3. Press and hold Right arrow for five seconds, press
Enter when display flashes reset.
Note: If Enter is not pressed within three seconds, the display
returns to the Diagnostics menu.
4. The meter goes through an initialization sequence (similar as on
power-up), and loads the factory default settings.