Model PD6060 Dual-Input Process Meter

Instruction Manual

12

RELAY RESET

User selectable via front panel buttons or digital inputs

1.

Automatic reset only (non-latching), when the input
passes the reset point.

2.

Automatic + manual reset at any time (non-latching)

3.

Manual reset only, at any time (latching)

4.

Manual reset only after alarm condition has cleared (L)

Note: Front panel button or digital input may be assigned to

acknowledge relays programmed for manual reset.

TIME DELAY

0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay

FAIL-SAFE
OPERATION

Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.

In case of power failure, relay will go to alarm state.

AUTO
INITIALIZATION

When power is applied to the meter, relays will reflect the
state of the input to the meter.

Isolated 4-20 mA Transmitter Output

OUTPUT
SOURCE

Process channel A, B, or C, max or min for channel A, B, or
highest or lowest max or min of A and B, set points 1-8,
Modbus input, or manual control mode

SCALING RANGE

1.000 to 23.000 mA for any display range

CALIBRATION

Factory calibrated: 4.000 to 20.000 = 4-20 mA output

ANALOG OUT
PROGRAMMING

23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break

ACCURACY

± 0.1% of span ± 0.004 mA

TEMPERATURE
DRIFT

0.4 µA/

°C max from 0 to 65°C ambient,

0.8 µA/

°C max from -40 to 0°C ambient

Note: Analog output drift is separate from input drift.

ISOLATED
TRANSMITTER
POWER SUPPLY

Terminals I+ & R: 24 VDC

± 5% @ 40 mA maximum; may

be used to power the 4-20 mA output or other devices.
Refer to Figure 5 on page 19 and Figure 14 on page 23.

EXTERNAL LOOP
POWER SUPPLY

35 VDC maximum

OUTPUT LOOP
RESISTANCE

Power supply

Minimum

Maximum

24 VDC

10

Ω 700

Ω

35 VDC (external)

100

Ω 1200

Ω