Precision Digital PD6060 User Manual
Page 38

Model PD6060 Dual-Input Process Meter
Instruction Manual
38
Additional parameters, not needed for most applications, are
programmed in the Advanced Features menu; see Advanced Features
Menu
, page 66.
Multi-Point Calibration & Scaling
The meter is set up at the factory for 2-point linear calibration. The
number of points for multi-point calibration/scaling is set up in the
Advanced
Features menu. Up to 32 linearization points may be
selected. See page 75 for details.
MeterView
®
Pro Software
The meter can also be programmed using the PC-based MeterView Pro
software available for free download at www.predig.com.
Data logging for one meter at the time is available with MeterView Pro
software. More advanced data acquisition may be accomplished by
using any Modbus RTU compliant software.
In order to program the meter using a computer, the meter must be
connected using a USB, RS-232, or RS-485 serial adapter, see
ORDERING INFORMATION on page 7 for details.
Scaling the Meter without a Signal Source
The process inputs (4-20 mA,
±10 VDC) can be scaled to display the
process variables in engineering units.
A signal source is not needed to scale the meter; simply program the
inputs and corresponding display values.