Model PD6060 Dual-Input Process Meter

Instruction Manual

69

Display Parameter Action/Setting

Calib

Calibrate

Calibrate 4-20 mA output (internal reference
source used for scaling the output)

4 nmA

4 mA output

Enter mA output value read by milliamp
meter with at least 0.001 mA resolution

20 nmA

20 mA output

Enter mA output value read by milliamp
meter with at least 0.001 mA resolution

User

User I/O

Assign function keys and digital I/O

F1

F1 function key

Assign F1 function key

F2

F2 function key

Assign F2 function key

F3

F3 function key

Assign F3 function key

F4

F4 function key

Assign F4 function key (digital input)

dI I

Digital input 1

Assign digital input 1 – 8, if expansion
modules are connected

dO 1

Digital output 1

Assign digital output 1 – 8, if expansion
modules are connected

ICal

Internal
calibration

Enter internal calibration (used for
recalibrating the meter with a calibrated
signal source)

Ch-A

Channel A

Perform calibration on channel A

Ch-b

Channel B

Perform calibration on channel B

C CAL

Current
calibration

Calibrate 4-20 mA current input (internal
reference source used for scaling the input)

C lo

Current low

Calibrate low current input (e.g. 4 mA)

C Hi

Current high

Calibrate high current input (e.g. 20 mA)

v CAL

Voltage
calibration

Calibrate voltage input

v Lo

Voltage low

Calibrate low voltage input (e.g. 0 V)

v Hi

Voltage high

Calibrate high voltage input (e.g. 10 V)

Copy

Copy

Enter copy function

Send

Send

Send meter settings to another meter

Done

Done

Copy function completed

Diag

Diagnostics

Display parameter settings