Relays – Precision Digital PD6060 User Manual
Page 11

Model PD6060 Dual-Input Process Meter
Instruction Manual
11
MULTI-POINT 
LINEARIZATION 
2 to 32 points for channel A and B
PROGRAMMA-
BLE EXPONENT 
1.0001 to 2.9999
LOW-FLOW 
CUTOFF 
0-999999 (0 disables cutoff function)
DECIMAL POINT
Up to five decimal places or none:
d.ddddd
, d.dddd, d.ddd, d.dd, d.d,
or
dddddd
CALIBRATION 
RANGE 
Input 
Range 
Minimum Span 
Input 1 & Input 2 
4-20 mA 0.15 mA 
±10 V 
0.10 V
An Error message will appear if the input 1 and input 2 
signals are too close together. 
INPUT 
IMPEDANCE 
Voltage ranges: greater than 500 k
Ω
Current ranges: 50 - 100
Ω
(depending on resettable fuse impedance)
INPUT 
OVERLOAD 
Current input protected by resettable fuse, 30 VDC max. 
Fuse resets automatically after fault is removed. 
F4 DIGITAL INPUT 
CONTACTS 
3.3 VDC on contact. Connect normally open contacts 
across F4 to COM. 
F4 DIGITAL INPUT 
LOGIC LEVELS 
Logic High: 3 to 5 VDC 
Logic Low: 0 to 1.25 VDC 
Relays
RATING
2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) 
external; rated 3 A @ 30 VDC and 125/250 VAC resistive 
load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads 
NOISE 
SUPPRESSION 
Noise suppression is recommended for each relay contact 
switching inductive loads; see page 22 for details. 
DEADBAND
0-100% of span, user programmable
HIGH OR LOW 
ALARM 
User may program any alarm for high or low trip point. 
Unused alarm LEDs and relays may be disabled (turn off). 
RELAY 
OPERATION 
Automatic (non-latching) 
Latching (requires manual acknowledge) 
Sampling (based on time) 
Pump alternation control (2 to 8 relays) 
Off (disable unused relays and enable Interlock feature) 
Manual on/off control mode 