Single-Compressor Module

Installation

2.6 Electrical Controls

2.6.1 General Considerations

All shutdown devices are dry contact switches rated Class I, Division II that are wired to a terminal box

for connection to the packager supplied control circuit. The common wires on all switches are connected

together. All switches are closed unless a fault condition is detected.

All safety and protective devices must be installed and used in accordance with applicable codes and

regulations.

Switches

All switch connections are wired to terminal strips in a junction box on the Compressor Module.

Switch

Status

• Low Inlet Gas Pressure

Normally Open, closes on pressure rise

• High Discharge Gas Pressure Normally Closed, opens on pressure rise
• High Temperature

Normally Closed, opens on temperature rise

Electrical Considerations - Variable Speed Compressor Module

• Compressor power for a variable speed Compressor Module is the

Variable Frequency Drive (VFD).

• Compressor speed control can be either a 4-20 mA or 0-10V signal (transducer supplied by customer)

applied to the VFD. Speed can also be manually controlled with a potentiometer or the VFD can be

set for a fixed speed.

• The Compressor is protected by the VFD.
• The customer control circuit must supply an

Enable signal to the VFD before the drive will accept a

Run Fwd signal.

• The VFD will start when the

Enable signal is on and a Run Fwd signal is applied.

• The VFD will stop if the

Run Fwd signal is off or the Enable signal is removed.

NOTE

The drive provides 24V for the

Enable and Run Fwd signals.

The installer must connect the

Enable and Run Forward terminals to the drive’s 24V terminal.