Maintenance 51

Emerson Energy Systems

Rectifier 200I/48

NT5C05C Installation and User Manual

Procedure 11 - Calibrating the meter

Step Action

1

Make sure the remote sense leads are disconnected by removing
the corresponding RC

fuse from the controller.

2

Set the VOLT/AMP switch to AMP. Set the output load of the plant
so the rectifier delivers a current of approximately 100 A. Measure
the voltage between VOUT+ and VOUT

, located on the front panel,

with a digital meter.

3

Convert this measured voltage to a current value ( 50 mV
corresponding to 250 A ).

current = 250 A

voltage 50

mV

If the voltage measured is 20.2 mV :

measured current

= 250 A X ( 20.2 mV ) = 101 A

50 mV

Rotate the CUR CAL potentiometer on the display panel until this
value is displayed.

4

Put the VOLT / AMP switch to VOLT. Adjust the V CAL
potentiometer so that the reading displayed on the meter of the
rectifier is identical to the reading on the digital meter.

5

Put the rectifier to OFF and reconnect the sense leads.

end

6.4.

Resetting the rectifier after an HVSD ( high voltage shutdown )

To reset the rectifier after an HVSD condition has occurred execute one of
the steps contained in Procedure 12.

Procedure 12 - Resetting the rectifier after a high voltage shutdown

Step Action

Locally

1

Toggle the ac circuit breaker on the unit itself, or the associated ac
breaker in the distribution panel OFF and ON ( wait until the green ac
ON LED extinguishes before toggling the breaker back to ON ).

Remotely

2

Apply a ground signal at the HVSDR input of the rectifier.

end