UM5C05C P0745680 Standard 6.00 October 2001

Emerson Energy Systems

4.2.3. Front panel LEDs

Table 10 - Designation of the LEDs on the front panel

LED Color

Description

AC ON

Green

Input ac voltage operational

CL Yellow

Current

Limit

EQL

Yellow

Rectifier is in equalize mode

FAN ALM

Red

Fan fail alarm

HVSD

Red

High voltage shutdown

RFA

Red

Rectifier fail alarm

SEN FAIL

Red

Remote sense fail

THSD Red

Thermal

shutdown

AC ON ( ac voltage monitoring )

The rectifier monitors the input voltage and if the voltage exceeds the set
limit, it will inhibit its operation and trigger a rectifier failure alarm
( RFA ). The rectifier will resume its normal operation automatically when
the specified input voltage has been re-established.

CL ( current limit indicator )

This LED lights up if the rectifier is in current limit. The rectifier limits
the output current to 205 A + 5 A ( adjusted in the factory ), 50% to 105%
of the rated output current.

EQL ( equalize )

Indicates the rectifier is in equalizing mode.

FAN ALM ( fan failure alarm )

This LED lights up when the FAN ALM is activated due to a defect in the
fan system. The fan configuration includes redundancy to ensure the
rectifier will continue working properly if one of the fans fails. If only one
fan fails, a rectifier failure alarm RFA will not be triggered. It is, however,
imperative to repair or change the fan unit as soon as possible to preserve
this redundant feature.