24 Installation

UM5C05C P0745680 Standard 6.00 October 2001

Emerson Energy Systems

3.5.1. Securing the dc output terminals to the busbars in a 1200 A

cabinet

For cabinet applications, no dc cabling is required; the output terminals of
the rectifier are connected directly to the busbars.

Procedure 3 - Securing the dc output terminals to the busbars of the

cabinet

Step Action

1

Connect the BAT GRD output terminal of the rectifier to the BR
busbar, and the –48 V output terminal of the rectifier to the –48 V
busbar located at the rear of the cabinet.

2

Tighten the bolts by applying a torque of 6.5

±

0.5 ft-lbs ( 8.5

±

0.5 N-m ).

end

3.5.2. Running and connecting the dc between busbars and a

rectifier

For frame applications, use terminal lug A0361762, supplied with the unit,
and no. 110 ( 4/0 ) metric cable.

Procedure 4 - Typical dc cabling in a frame application

Step Action

1

Connect the BAT GRD output terminal of the rectifier to the CHG
GRD busbar of the power plant. Connect the –48 V output terminal
of the rectifier to the CHG / DISCH BAT busbar of the power plant
( see Figure 5 ).

2

Apply a torque of 6.5

±

0.5 ft-lbs ( 8.5

±

0.5 N-m ) on the bolts

securing the lugs to the rectifier terminals.

end

3.6.

Connecting ac to the rectifiers

WARNING

Electrical connections should meet standards

The electrical installation must be carried out by qualified
personnel and in accordance with local electrical codes.