Jordan Valve Mark ED & ET Series (8) Globe Style Control Valve User Manual
Page 6

-6-
Making Up the Stem Connection Cont.,
Reverse-Acting Actuators
1.
Close the valve plug ensuring the valve plug is on
the seat.
2.
Supply enough spring force to the actuator stem to
ensure the actuator is in full “Down” position. In-
crease the loading pressure to the diaphragm case
to allow the actuator stem to rise sufficiently so the
locknuts can be screwed onto the valve plug stem.
Thread the locknuts down on the valve plug stem
as far as possible. Set the travel indicator on the
locknuts, “cupped” edge downward.
3.
Slowly release the pressure in the diaphragm case,
allowing the actuator to return to the full down posi-
tion. Measure the distance between the lower end
of the actuator stem and the travel indicator disc.
4.
Increase the load on the actuator, causing the stem
to rise up by approximately 1/8”. Using the two-
piece stem connector and cap screws, secure the
actuator stem and valve plug stem together.
5.
Move the travel indicator disc against the bottom of
the stem connector.
6.
Secure the disc with the upper locknut. Change the
travel indicator scale so that it reads closed.
7.
Open the valve plug by increasing the diaphragm
loading pressure. Secure the lower stem locknut
against the upper locknut. The connection is now
complete.
8.
To increase travel see “To increase desired length of
travel” instructions.
P
arts
o
rderIng
A serial number identifies every Mark E Series valve
body-bonnet assembly, which can be found on the front
of the valve. Please refer to this number when contact-
ing your Jordan Valve representative.
M
ark
ED
anD
ET S
EriES
8-
inch
G
lobE
S
TylE
c
onTrol
V
alVES