4.3 Drive Monitoring
This section describes the objects used to monitor the drive. Refer to the appropriate Technical Manual for
additional information.
4.3.1 Operating Status – AI1-AI13, BI1-BI8
The following table summarizes the input objects available for monitoring the operating status of the drive.
Operating Variable
Object ID
Description
Speed Reference
AI1
Reports the speed reference as commanded from the source selected by
AO8 (operator, terminal, or network). This allows speed reference to be
monitored even when the network is not the command source.
This value matches AO1 only when the network is selected as the command
source (AO8 = 4,5,6).
Output Speed
AI2
Reports output speed.
Output Current
AI3
Reports output current.
Output Power
AI5
Reports output power. This object is only available on GPD506 drives.
Drive Temperature
AI6
Reports drive temperature. This object is only available on GPD506
drives.
AC Output Voltage
AI8
Reports AC output voltage (i.e. voltage applied to motor).
DC Bus Voltage
AI9
Reports DC bus voltage.
Kilowatt Hour Meter
AI4
Reports cumulative drive energy usage in kilowatts. This object is only
available on GPD506 drives.
Megawatt Hour Meter
AI13
Reports cumulative drive energy usage in megawatts. This object is only
available on GPD506 drives.
PID Feedback
AI7
Reports PID feedback. If PID is disabled, this value will be zero. This
object is only available on GPD506 drives.
Elapsed Timer – Hrs
AI11
Reports cumulative run time in hours.
Elapsed Timer – 10K
Hrs
AI12
Reports cumulative run time in increments of 10K hours.
Fault Code
AI10
Reports drive fault status. This value is the decimal equivalent of a binary
fault word. It is the sum of the values associated with each fault bit, as listed
below:
Fault
Bit
Value
Overcurrent, Ground, Short Circuit
0
1
Overvoltage
1
2
Drive
Overload
2
4
Overheat
3
8
Main
Circuit
5
32
Brake
Transistor
6
64
External
7
128
Hardware
8
256
Motor
Overload
9
512
During Undervoltage
11
2048
Power Loss
12
4096
Phase
13
8192
Run Status
BI1
Reports the run status (1=Run) as commanded from the source selected by
AO8 (operator, terminal, or network). This allows the status to be monitored
even when the network is not the command source.
This value matches BO1 only when the network is selected as the command
source (AO8 = 6,7,8).
Forward/Reverse
Status
BI2
Reports the forward/reverse status (1=Reverse) as commanded from the
source selected by AO8 (operator, terminal, or network). This allows the
status to be monitored even when the network is not the command source.
This value matches BO2 only when the network is selected as the command
source (AO8 = 6,7,8).
Drive Ready Status
BI3
Reports whether or not the drive is ready to accept a run command
(1=Ready).
Fault Status
BI4
Reports the drive fault status (1=Fault).