4.3 Drive Monitoring

This section describes the objects used to monitor the drive. Refer to the appropriate Technical Manual for
additional information.

4.3.1 Operating Status – AI1-AI13, BI1-BI8

The following table summarizes the input objects available for monitoring the operating status of the drive.

Operating Variable

Object ID

Description

Speed Reference

AI1

Reports the speed reference as commanded from the source selected by
AO8 (operator, terminal, or network). This allows speed reference to be
monitored even when the network is not the command source.

This value matches AO1 only when the network is selected as the command
source (AO8 = 4,5,6).

Output Speed

AI2

Reports output speed.

Output Current

AI3

Reports output current.

Output Power

AI5

Reports output power. This object is only available on GPD506 drives.

Drive Temperature

AI6

Reports drive temperature. This object is only available on GPD506
drives.

AC Output Voltage

AI8

Reports AC output voltage (i.e. voltage applied to motor).

DC Bus Voltage

AI9

Reports DC bus voltage.

Kilowatt Hour Meter

AI4

Reports cumulative drive energy usage in kilowatts. This object is only
available on GPD506 drives.

Megawatt Hour Meter

AI13

Reports cumulative drive energy usage in megawatts. This object is only
available on GPD506 drives.

PID Feedback

AI7

Reports PID feedback. If PID is disabled, this value will be zero. This
object is only available on GPD506 drives.

Elapsed Timer – Hrs

AI11

Reports cumulative run time in hours.

Elapsed Timer – 10K

Hrs

AI12

Reports cumulative run time in increments of 10K hours.

Fault Code

AI10

Reports drive fault status. This value is the decimal equivalent of a binary
fault word. It is the sum of the values associated with each fault bit, as listed
below:

Fault

Bit

Value

Overcurrent, Ground, Short Circuit

0

1

Overvoltage

1

2

Drive

Overload

2

4

Overheat

3

8

Main

Circuit

5

32

Brake

Transistor

6

64

External

7

128

Hardware

8

256

Motor

Overload

9

512

During Undervoltage

11

2048

Power Loss

12

4096

Phase

13

8192

Run Status

BI1

Reports the run status (1=Run) as commanded from the source selected by
AO8 (operator, terminal, or network). This allows the status to be monitored
even when the network is not the command source.

This value matches BO1 only when the network is selected as the command
source (AO8 = 6,7,8).

Forward/Reverse

Status

BI2

Reports the forward/reverse status (1=Reverse) as commanded from the
source selected by AO8 (operator, terminal, or network). This allows the
status to be monitored even when the network is not the command source.

This value matches BO2 only when the network is selected as the command
source (AO8 = 6,7,8).

Drive Ready Status

BI3

Reports whether or not the drive is ready to accept a run command
(1=Ready).

Fault Status

BI4

Reports the drive fault status (1=Fault).