EMC Guidelines Compliance

This drive is tested according to European standards IEC/EN 61800-3: 2004.

n

EMC Filter and DC Link Chokes for IEC/EN 61000-3-2 Compliance

EMC filter and DC link choke requirements must be met to ensure continued compliance with CE guidelines.

NOTICE

Refer to the P1000 Technical Manual SIEPYAIP1U01 on the CD-ROM packaged with the product for more information on
EMC Filter Installation and complete product instructions necessary for proper installation, set-up, troubleshooting and
maintenance. CD part number TOECC71061615.

u

Drive Derating Data

n

Single-Phase Derating

P1000 drives are optimized and compatible for use with both three-phase and single-phase input power supplies. The P1000

output to the motor is fixed at three-phase.
P1000 output capacity to the motor is reduced or derated when single-phase input power is used.
Refer to the drive Technical Manual - Drive Derating Data section to assist in model selection when using the drive in

single-phase input power applications.

n

Rated Current Depending on Carrier Frequency

Normal Duty Rating (ND)

Increasing the carrier frequency above 2 kHz will reduce the ND rated output current of the drive.

NOTICE

Refer to the P1000 Technical Manual – Drive Derating Data section to assist in model selection and adjustment when the
application requires changing the drive carrier frequency from factory defaults.

u

Temperature Derating

To ensure the maximum performance life, the drive output current must be derated as shown in

Figure i.29

when the drive is

installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. In order to ensure reliable

drive overload protection, set parameters L8-12 and L8-35 according to the installation conditions.

n

Parameter Settings

No.

Name

Description

Range

Def.

L8-12

Ambient

Temperature Setting

Adjust the drive overload (oL2) protection level when the drive is installed

in an environment that exceeds its ambient temperature rating.

-10 to +50

+40 °C

L8-35

Installation Method

Selection

0: IP00/Open-Chassis Enclosure

1: Side-by-Side Mounting

2: IP20/NEMA Type 1 Enclosure

3: Finless Drive or External Heatsink Installation

0 to 3

<1>

<1> Default setting is determined by drive model.

Setting 0: (Models 2A0250 to 2A0415 and 4A0208 to 4A1200)
Setting 2: (Models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242).

Setting 0: IP00/Open-Chassis Enclosure

Drive operation between -10 °C and +50 °C allows 100% continuous current without derating.

Setting 1: Side-by-Side Mounting

Drive operation between -10 °C and +30 °C allows 100% continuous current without derating. Operation between +30 °C and

+50 °C requires output current derating.