Wiring the control circuit terminal – Yaskawa CIMR-PU User Manual

Page 38

background image

n

Serial Communication Terminals

Table i.11 Control Circuit Terminals: Serial Communications

Type

No.

Signal Name

Function (Signal Level)

MEMOBUS/Modbus
Communication

<1>

R+

Communications input (+)

MEMOBUS/Modbus communication: Use an

RS-422 or RS-485 cable to connect the drive.

RS-422/RS-485

MEMOBUS/Modbus

communication

protocol

115.2 kbps (max.)

R-

Communications input (-)

S+

Communications output (+)

S-

Communications output (-)

IG

Shield ground

0 V

<1> Enable the termination resistor in the last drive in a MEMOBUS/Modbus network by setting DIP switch S2 to the ON position. Refer to the manual

section on Control I/O Connections for more information.

n

Control Circuit Wire Size and Torque Specifications

Select appropriate wire type and gauges from

Table i.12

. For simpler and more reliable wiring, use crimp ferrules on the wire

ends. Refer to the Technical Manual on the CD-ROM packaged with the drive for ferrule terminal types and sizes.

Table i.12 Wire Gauges

Terminal

Screw

Size

Tightening

Torque

N•m

(lb. in)

Bare Wire Terminal

Ferrule-Type Terminal

Wire Type

Applicable

wire size

mm

2

(AWG)

Recomm.

wire size

mm

2

(AWG)

Applicable

wire size

mm

2

(AWG)

Recomm.

wire size

mm

2

(AWG)

S1-S8, SC, SN, SP

M3

0.5 to 0.6

(4.4 to 5.3)

Stranded wire:

0.2 to 1.0

(24 to 16)

Solid wire:

0.2 to 1.5

(24 to 16)

0.75 (18)

0.25 to 0.5

(24 to 20)

0.5 (20)

Shielded wire,

etc.

RP, V+, A1, A2, A3,

AC, 24 V
MA, MB, MC, MD, ME,

MF
M1-M4
FM, AM, AC
R+, R-, S+, S-, IG

u

Wiring the Control Circuit Terminal

This section describes the proper procedures and preparations for wiring the control terminals.

WARNING!

Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could result

in death or serious injury.
NOTICE:

Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, ⊖, ⊕1, ⊕2) and

other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.
NOTICE:

Separate wiring for digital output terminals MA, MB, MC, MD, ME, MF and M1 to M4 from wiring to other control circuit lines.

Improper wiring practices could result in drive or equipment malfunction or nuisance trips.
NOTICE:

Use a class 2 power supply when connecting to the control terminals. Improper application of peripheral devices could result in

drive performance degradation due to improper power supply. Refer to NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control,

Signaling, and Power Limited Circuits for requirements concerning class 2 power supplies.
NOTICE:

Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices could

result in drive or equipment malfunction due to short circuit.
NOTICE:

Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive or

equipment malfunction or nuisance trips.
NOTICE:

Do not tighten screws beyond the specified tightening torque. Failure to comply may result in erroneous operation, damage to the

terminal block, or cause a fire.
NOTICE:

Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or

equipment malfunction due to electrical interference.

Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete.

Refer to

Terminal Board Wiring Guide on page 39

for details. Prepare the ends of the control circuit wiring as shown in

Figure i.

16

.

Refer to Wire Gauges on page 38

.

Connect control wires as shown in

Figure i.14

and

Figure i.15

.

i.3 Electrical Installation Safety

38

YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions