Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

2A0415

R/L1, S/L2, T/L3

350 × 2P

250 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

300 × 2P

300 to 600

⊖, ⊕1

300 to 600

⊕3

3/0 to 600

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.
<2> Install a GFCI, or use 10 mm

2

(AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.

Note:

When connecting peripheral devices or options to terminals

⊖, ⊕1, ⊕3, B1, and B2, refer to the instruction manual for each device. For

more information, contact Yaskawa or your nearest sales representative.

n

Three-Phase 400 V Class

Table i.6 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)

Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

4A0002
4A0004

R/L1, S/L2, T/L3

14

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

12

<1>

14 to 12

4A0005
4A0007
4A0009

R/L1, S/L2, T/L3

14

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

<1>

14 to 10

4A0011

R/L1, S/L2, T/L3

12

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

<1>

14 to 10

4A0018

R/L1, S/L2, T/L3

10

12 to 6

M4

2.1 to 2.3

(18.6 to 20.4)

U/T1, V/T2, W/T3

10

12 to 6

⊖, ⊕1, ⊕2

12 to 6

B1, B2

12 to 10

10

<1>

14 to 10

M5

2.0 to 2.5

(17.7 to 22.1)

4A0023

R/L1, S/L2, T/L3

10

10 to 6

M4

2.1 to 2.3

(18.6 to 20.4)

U/T1, V/T2, W/T3

10

10 to 6

⊖, ⊕1, ⊕2

12 to 6

B1, B2

12 to 10

10

<1>

12 to 10

M5

2.0 to 2.5

(17.7 to 22.1)

4A0031

R/L1, S/L2, T/L3

8

8 to 6

M5

3.6 to 4.0

(31.8 to 35.4)

U/T1, V/T2, W/T3

8

10 to 6

⊖, ⊕1, ⊕2

10 to 6

B1, B2

10 to 8

2.7 to 3.0

(23.9 to 26.6)

8

<2>

10 to 8

M6

5.4 to 6.0

(47.8 to 53.1)